Data given are
kV – 0.24
Indicated IR – 2MΩ
Temp. - 30°C
Correction factor – 0.5
Recommended value (Rm) = kV + 1 MΩ
= 0.24 + 1
= 1.24 MΩ
Indicated IR at 30°C = 2MΩ
Correction factor – 0.5
So value corrected to 40°C = Rm = kt * Rt
= 0.5 * 2
= 1MΩ
The generator cannot be put in service because the corrected value is lesser than recommended value. It should be sent for IR re-conditioning .